High-Efficiency Axial Flow Fan Unit Cooler from China Suppliers - Durable Design, Versatile Refrigerant Compatibility
Product Features
1. Casing
Adopt high-quality steel plate with powder coating RAL9003. Hinged structure is adopted for both side plates and external drip tray, which is convenient and quick to operate.
2. Heat Exchanger Coil
Copper tubing Φ12, spacing 38.1x33; Corrugated aluminium fins, fin spacing 4.2mm and 6.4mm and 9.0mm.
3. Fans
Axial fans with High wind circle, working temperature -40℃~60℃. High air duct design with integral stretching, good ventilation effect, further airthrow, lower noise. Fans individually connected to junction box. Fan blade φ300, φ350, φ400, φ500, standard 4-pole motor.
4. Defrosting
Standard use of electric defrosting, stainless heating pipes installed in the middle of coil and inner water plate. Independent electric heating tube junction box. Hot gas defrosting or coil hot gas defrosting can also be used.
5. Refrigerants
It can meet the requirements of R404A, R507A, R448A, R449A, R134a, R22 and other refrigerants.
Technical Data
| MODEL | Nomiral capacity (W) |
Cooling Area (m²) |
Fin Space (mm) |
pipe diameten (mm) |
Axial flow fan | Defrost electrical heater | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Quantity (set) |
Diameter of fans (mm) |
Air volume (m³/h) |
wind pressure (mmH₂O) |
Power (w) |
Voltage (V) |
Coli (kw) |
Drain water plate (kW) |
Voltage (V) |
|||||
| DJZ-8.9/55 | 8900 | 55 | 9 | 16 | 2 | 500 | 2×6000 | 167 | 2×750 | 380 | 4.5 | 1.5 | 220 |
| DJZ-11.6/70 | 11600 | 70 | 9 | 16 | 3 | 500 | 3×6000 | 167 | 3×750 | 380 | 8.4 | 2.1 | 220 |
| DJZ-14.3/85 | 14300 | 85 | 9 | 16 | 3 | 500 | 3×6000 | 167 | 3×750 | 380 | 8.4 | 2.1 | 220 |
| DJZ-17.1/100 | 17100 | 100 | 9 | 16 | 3 | 500 | 3×6000 | 167 | 3×750 | 380 | 11.2 | 2.8 | 220 |
| DJZ-19.6/115 | 19600 | 115 | 9 | 16 | 4 | 500 | 4×6000 | 167 | 4×750 | 380 | 11.2 | 2.8 | 220 |
| DJZ-22/130 | 22000 | 130 | 9 | 16 | 4 | 500 | 4×6000 | 167 | 4×750 | 380 | 12 | 3 | 380 |
| ZDJ-23/140 | 23000 | 140 | 9 | 16 | 2 | 600 | 2x12000 | 167 | 2x1500 | 380 | 24 | 3 | 380 |
| ZDJ-25/150 | 25000 | 150 | 9 | 16 | 2 | 600 | 2x12000 | 167 | 2x1500 | 380 | 24 | 3 | 380 |
| ZDJ-28/170 | 28000 | 170 | 9 | 16 | 3 | 600 | 3x12000 | 167 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDJ-30/190 | 30000 | 190 | 9 | 16 | 3 | 600 | 3x12000 | 295 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDJ-35/210 | 35000 | 210 | 9 | 16 | 3 | 600 | 3x12000 | 295 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDJ-41/250 | 41000 | 250 | 9 | 16 | 4 | 600 | 4x12000 | 295 | 4x1500 | 380 | 27 | 3 | 380 |
| ZDJ-50/300 | 50000 | 300 | 9 | 16 | 4 | 600 | 4x12000 | 295 | 4x1500 | 380 | 30 | 3 | 380 |
| DDZ-14.9/80 | 14900 | 80 | 6 | 16 | 2 | 500 | 2×6000 | 167 | 2×750 | 380 | 4.5 | 1.5 | 220 |
| DDZ-18.7/100 | 18700 | 100 | 6 | 16 | 3 | 500 | 3×6000 | 167 | 3×750 | 380 | 8.4 | 2.1 | 220 |
| DDZ-22.4/120 | 22400 | 120 | 6 | 16 | 3 | 500 | 3×6000 | 167 | 3×750 | 380 | 8.4 | 2.1 | 220 |
| DDZ-26.4/140 | 26400 | 140 | 6 | 16 | 3 | 500 | 3×6000 | 167 | 3×750 | 380 | 11.2 | 2.8 | 220 |
| DDZ-30.0/160 | 30000 | 160 | 6 | 16 | 4 | 500 | 4×6000 | 167 | 4×750 | 380 | 11.2 | 2.8 | 220 |
| DDZ-35.0/180 | 35000 | 180 | 6 | 16 | 4 | 500 | 4×6000 | 167 | 4×750 | 380 | 12 | 3 | 380 |
| ZDD-37.0/200 | 37000 | 200 | 6 | 16 | 2 | 600 | 2x12000 | 167 | 2x1500 | 380 | 24 | 3 | 380 |
| ZDD-40.0/220 | 40000 | 220 | 6 | 16 | 2 | 600 | 2x12000 | 167 | 2x1500 | 380 | 24 | 3 | 380 |
| ZDD-46.0/250 | 46000 | 250 | 6 | 16 | 3 | 600 | 3x12000 | 167 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDD-50.0/275 | 50000 | 275 | 6 | 16 | 3 | 600 | 3x12000 | 295 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDD-57.0/310 | 57000 | 310 | 6 | 16 | 3 | 600 | 3x12000 | 295 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDD-67.0/360 | 67000 | 360 | 6 | 16 | 4 | 600 | 4x12000 | 295 | 4x1500 | 380 | 27 | 3 | 380 |
| ZDD-81.0/440 | 81000 | 440 | 6 | 16 | 4 | 600 | 4x12000 | 295 | 4x1500 | 380 | 30 | 3 | 380 |
| DLZ-21.0/105 | 21000 | 105 | 4.5 | 16 | 2 | 500 | 2×6000 | 167 | 2×750 | 380 | 3 | 1.5 | 220 |
| DLZ-25.0/135 | 25000 | 135 | 4.5 | 16 | 3 | 500 | 3×6000 | 167 | 3×750 | 380 | 6.3 | 2.1 | 220 |
| DLZ-32.6/160 | 32600 | 160 | 4.5 | 16 | 3 | 500 | 3×6000 | 167 | 3×750 | 380 | 6.3 | 2.1 | 220 |
| DLZ-37.6/185 | 37600 | 185 | 4.5 | 16 | 3 | 500 | 3x6000 | 167 | 3x750 | 380 | 8.4 | 2.8 | 220 |
| DLZ-42.7/220 | 42700 | 220 | 4.5 | 16 | 4 | 500 | 4x6000 | 167 | 4x750 | 380 | 8.4 | 2.8 | 220 |
| DLZ-50.0/250 | 50000 | 250 | 4.5 | 16 | 4 | 500 | 4x6000 | 167 | 4x750 | 380 | 9 | 3 | 380 |
| ZDL-55.0/280 | 55000 | 280 | 4.5 | 16 | 2 | 600 | 2x12000 | 167 | 2x1500 | 380 | 24 | 3 | 380 |
| ZDL-60.0/300 | 60000 | 300 | 4.5 | 16 | 2 | 600 | 2x12000 | 167 | 2x1500 | 380 | 24 | 3 | 380 |
| ZDL-66.0/330 | 66000 | 330 | 4.5 | 16 | 3 | 600 | 3x12000 | 167 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDL-70.0/375 | 70000 | 375 | 4.5 | 16 | 3 | 600 | 3x12000 | 295 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDL-82.0/410 | 82000 | 410 | 4.5 | 16 | 3 | 600 | 3x12000 | 295 | 3x1500 | 380 | 24 | 3 | 380 |
| ZDL-94.0/470 | 94000 | 470 | 4.5 | 16 | 4 | 600 | 4x12000 | 295 | 4x1500 | 380 | 27 | 3 | 380 |
| ZDL-116.0/580 | 116000 | 580 | 4.5 | 16 | 4 | 600 | 4x12000 | 295 | 4x1500 | 380 | 30 | 3 | 380 |
DJ Cooling Capacity: Based on an air inlet dry-bulb temperature of -25℃, evaporation temperature of -31℃, and refrigerant liquid temperature of 20℃.
DD Cooling Capacity: Based on an air inlet dry-bulb temperature of -18℃, evaporation temperature of -25℃, and refrigerant liquid temperature of 20℃.
DL Cooling Capacity: Based on an air inlet dry-bulb temperature of 0℃, evaporation temperature of -8℃, and refrigerant liquid temperature of 30℃.
Product Display
Installation dimensions
| MODEL | L | D | D2 | F | E1 | N | H | Inlet | Cycle pipe | Water outlet |
|---|---|---|---|---|---|---|---|---|---|---|
| DDZ80/DLZ105/DJZ55 | 1780 | 880 | 490 | 152.5 | 737.5 | 2 | 720 | 19 | 38 | G1" |
| DDZ100/DLZ135/DJZ70 | 2230 | 880 | 490 | 152.5 | 641.5 | 3 | 720 | 22 | 50 | G1" |
| DDZ120/DLZ160/DJZ85 | 2230 | 945 | 555 | 152.5 | 641.5 | 3 | 720 | 22 | 50 | G1" |
| DDZ140/DLZ185/DJZ100 | 2920 | 880 | 490 | 197.5 | 841.5 | 3 | 720 | 22 | 50 | G1" |
| DDZ160/DLZ220/DJZ115 | 2920 | 945 | 555 | 197.5 | 631 | 4 | 720 | 22 | 50 | G1.5" |
| DDZ180/DLZ250/DJZ130 | 3250 | 945 | 555 | 187.5 | 718.5 | 4 | 720 | 25 | 50 | G1.5" |
| ZDD200/ZDL280/ZDJ140 | 2252 | 1140 | 775 | 186 | 925 | 2 | 885 | 25 | 50 | G1.5" |
| ZDD220/ZDL300/ZDJ150 | 2352 | 1140 | 775 | 186 | 976 | 2 | 885 | 25 | 50 | G1.5" |
| ZDD250/ZDL330/ZDJ170 | 2702 | 1140 | 775 | 186 | 766 | 3 | 885 | 25 | 50 | G1.5" |
| ZDD275/ZDL375/ZDJ190 | 2902 | 1140 | 775 | 186 | 833 | 3 | 885 | 25 | 50 | G1.5" |
| ZDD310/ZDL410/ZDJ210 | 3062 | 1140 | 775 | 186 | 886 | 3 | 885 | 25 | 50 | G1.5" |
| ZDD360/ZDL470/ZDJ250 | 3552 | 1140 | 775 | 186 | 787 | 4 | 935 | 25 | 50 | G1.5" |
| ZDD440/ZDL580/ZDJ300 | 3786 | 1140 | 775 | 186 | 846 | 4 | 1035 | 28 | 50 | G1.5" |
DJ Cooling Capacity: Based on an air inlet dry-bulb temperature of -25℃, evaporation temperature of -31℃, and refrigerant liquid temperature of 20℃.
DD Cooling Capacity: Based on an air inlet dry-bulb temperature of -18℃, evaporation temperature of -25℃, and refrigerant liquid temperature of 20℃.
DL Cooling Capacity: Based on an air inlet dry-bulb temperature of 0℃, evaporation temperature of -8℃, and refrigerant liquid temperature of 30℃.
Application
Frequently Asked Questions
Q1: Which refrigerants are compatible with these cooling units?
These units are highly versatile and compatible with a wide range of refrigerants, including R404A, R507A, R448A, R449A, R134a, R22, and other standard refrigerants.
Q2: What defrosting methods are supported by the system?
Electric defrosting is the standard configuration, utilizing stainless heating pipes installed in the middle of the coil and the inner water plate. However, hot gas defrosting or coil hot gas defrosting options can also be accommodated.
Q3: How are the axial fans designed for optimized performance?
The fans are designed with a high wind circle and work within a temperature range of -40℃ to 60℃. They feature an integral stretching high air duct design which ensures a better ventilation effect, longer airthrow, and significantly lower noise levels.
Q4: What are the primary differences between DJ, DD, and DL cooling capacities?
The models are calculated under different operating conditions: DJ is designed for low-temperature applications (inlet -25℃ / evap -31℃), DD for medium-low temperatures (inlet -18℃ / evap -25℃), and DL for high/medium temperatures (inlet 0℃ / evap -8℃).
Q5: What materials are used to construct the casing and heat exchanger coil?
The casing uses a high-quality steel plate finished with a powder coating in RAL9003. The heat exchanger coil is manufactured using Φ12 copper tubing with corrugated aluminum fins, offering optimized heat transfer.